KOMPARASI PENENTUAN LOKASI PEMASANGAN KAPASITOR ANTARA GI. DUMAI DAN GI. BAGAN SIAPI-API

M Wahyudi Hazri, Yulisman Yulisman, Aggrivina Dwiharzandis

Sari


During peak load conditions, significant voltage drops are observed in the Dumai transmission subsystem. The minimum voltages recorded at the Dumai, Bagan Siapi-api, and Dumai Industrial Area substations are 134.7 kV, 133.0 kV, and 131.1 kV, respectively, exceeding the permissible voltage deviation limits. To mitigate this condition, a shunt capacitor is designed and evaluated through modeling and simulation. Analytical and DigSILENT PowerFactory 2021 simulation results indicate that a 25 MVAR shunt capacitor installed at the Bagan Siapi-api Substation provides the most suitable compensation. The installation increases the bus voltage by 8.10 kV to 141.10 kV, corresponding to a voltage deviation of 5.93% from the nominal value. Furthermore, total system losses in the Riau subsystem are reduced from 20.63 MW and −352.8 MVAR to 19.88 MW and −366.8 MVAR, or reduction 0,75 MW. These results confirm that shunt capacitor integration effectively improves voltage profiles while reducing reactive power flow and system losses.

Keywords: shunt capacitor, substation, voltage drop, DIgSILENT PowerFactory 2021, voltage improvement, system losses


Teks Lengkap:

PDF

Referensi


Z.H.V. Zafiro and M. Haddin, "Analisis Rugi-rugi Daya dan Jatuh Tegangan Pada SUTT 150 kV Pekalongan-Comal dengan Menggunakan ETAP," Aviation Electronics, Information Technology, Telecommunications, Electricals, and Controls (AVITEC), Vol. 6, No. 2, pp. 159-167, 2024.

Z. Hendri, R.D. Fadilah, N. Harun, M.E.R. Ulum, R.W. Pratama and D. Corio, "Optimizing the Capacity of 150 kV Transmission Lines Through the Addition of Shunt Capacitors: Case Study at PT. PLN (Persero) West Sumatra Subsystem," Journal of Electrical Technology UMY, Vol. 8, No. 1, pp. 17-27, 2024.

KESDM, “Aturan Jaringan Sistem Tenaga Listrik (Grid Code),” Menteri Energi dan Sumber Daya Mineral, Republik Indonesia, 2020.

M. Saini, M. Y. Yunus, R. Akbar and M. Yassir, "Analaisis Jatuh Tegangan pada Sistem Kelistrikan 150 kV Sulselrabar Menggunakan Digsilent Powerfactory 15" SINERGI Vol. 16, No. 2, pp. 190-196, 2019.

S. Dali, I. Ridzki, R. Duanaputri and E. Maulana, "Analisis Pengaruh Penambahan Gardu Induk Terhadap Aliran Daya dan Profil Tegangan," Elposys: Jurnal Sistem Kelistrikan, Vol. 9, No. 2, pp. 58-63, 2022.

S. I. Haryudo and U. T. Kartini, "Analisis Perbandingan Perhitungan Short Circuit Pada Gardu Induk 150/20 kV (Studi Kasus Pada Gardu Induk Manyar Gresik)," JURNAL TEKNIK ELEKTRO, pp. 507-515, 2021.

M. F. Hakim, S. Nurhadi, H. D. F. Amaral, and S. L. Hermawan, “Kapasitor Shunt Sebagai Korektor Tegangan Bus di Gardu Induk,” Elposys: Jurnal Sistem Kelistrikan, Vol. 10, No. 1, pp. 30–35, 2023.

"IEEE Guide for the Application of Shunt Power Capacitors," IEEE, 2011.

PT.PLN (PERSERO), (2023). “Mandiri report (Data Impedansi dan Arus Hubung Singkat Gardu Induk)”. Sumber Data

A. Muntaha, I. Darmawan, A. Jaya, and D. Maulidyawati, “SIMULASI PERBAIKAN DROP TEGANGAN DAN SUSUT PADA GARDU INDUK ALAS DENGAN PENAMBAHAN KAPASITOR BANK,” Jurnal Informatika Teknologi DanSains (Jinteks), Vol. 7, No. 2, pp. 516-525, 2025.

T. Barlian, Y. Apriani, N. Savitri, and M. Hurairah, "Analisis Kapasitor Bank Untuk Memperbaiki Tegangan," JURNAL SURYA ENERGY, Vol. 4, No. 2, pp. 391-396, 2020.




DOI: https://doi.org/10.31869/rtj.v9i2.7911

Article Metrics

Sari view : 0 times
PDF - 0 times

Refbacks

  • Saat ini tidak ada refbacks.


##submission.copyrightStatement##

"Web Kunjungan Saat ini

Kunjungan Dari Negara

 Flag Counter

 

 

Creative Commons License
Rang Teknik Journal is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.